Visible break conforms to widely accepted
operating safety practice, giving clear visual confirmation
of contact position of ALL THREE PHASES through the
viewing windows in the tank. The large open gap allows
field voltage testing without cable removal.
Manual, Remote or Automatic Switching
Arc Whipper® is equipped for manual operation as
standard and includes: External handles for operation
by hand; quick make/break spring operators; bushing
oriented line diagram; positive position indicators;
padlock provisions; and operating instructions. Remote
operation can also be provided by motor operators with
pushbutton or SCADA control. Automatic transfer switches
use fast acting motor operators with voltage/current
sensing and full function control. Units are factory
wired/adjusted
Construction Features
Arc Whipper® SF6 loadbreak switches are ruggedly
constructed, incorporate proven design and are rated/tested
in accordance with ANSI standards C37.71-1984 and C37.72-1987
for long life with minimal maintenance. Switch contacts
are equipped with very high speed auxiliary arcing contacts
to quickly interrupt in ¼ to ½ cycle,
leaving main contact surfaces undamaged by arcing. The
arcing contact allows main contacts to be designed for
high continuous, fault close and momentary current performance.
Switches are factory filled with non-toxic, non-flammable,
high dielectric SF6 gas insulation. SF6 quality and
stability are maintained by use of totally sealed tank
construction, an internal purifying absorbent and the
extremely fast Arc Whipper® interrupter. A color
coded, field replaceable pressure gauge and self-sealing
fill valve allow monitoring and addition of SF6 as necessary.
Switch tanks are ¼ thick
steel with a highly corrosion/abrasion resistant 5 mil
epoxy finish. External fittings and fasteners are marine
grade stainless steel or bronze. For increased corrosion
resistance, stainless steel tanks can be provided.
Current carrying parts are high conductivity electrolytic
grade copper with plating, locking fasteners, and torque
wrench assembly to assure permanent low resistance connections.
Moving contacts are self-aligning, self cleaning (wiping
type) and designed to increase contact pressure with
increasing currents. Contact assemblies are supported
by high strength, molded glass polyester insulation
with flex connectors at critical locations to prevent
stressing and misaligning due to high current or mechanical
forces.
Ratings
Arc Whipper® SF6 loadbreak switches are designed,
tested and rated per applicable sections of IEEE, ANSI,
NEMA, CSA and other industry standards including:
ANSI C37.71-1984 Standard for Subsurface
Load Interrupting Switches.
ANSI C37.72-1987 Standard for Padmounted Load Interrupting
Switches.
ANSI/IEEE 386 Standard for Separable Connectors and
Bushings.
IEC 265 International Standards for Load Interrupting
Switches.
ASTM D-2472 Specification for Commercial Type Electrical
Grade SF6.
ANSI C57.12.28 Standard for Padmount Enclosures.
Note 35 kV information available on request
Application Information
Arc Whipper® SF6 loadbreak switches are completely
submersible, fully deadfront, and corrosion resistant
for application in the harshest conditions including
areas subject to flooding, severe contamination, rodents
and snakes, blowing snow/dust, sea coasts, high altitude,
and even Division 2 hazardous locations. Non-toxic,
non-flammable SF6 insulation permits installation indoors
or outdoors in high traffic areas. Compact size and
reduced weight provide solutions where overall space
is important such as in high-rise buildings, front lot
lines and in small vaults.
Switch Operators and Options
Arc Whipper® SF6 load break switches are equipped
with external handles for manual operation as standard.
The handle can be padlocked in all switch positions
and has an anti-reversing feature for additional safety.
Interlocks can be provided as may be required by local
practice and for increased safety. In addition, remote/SCADA
and fully automatic operators are available for increased
levels of control and system automation. These motor
operators attach to the switch handle and may be easily
disconnected for manual operation.
Manual Operation
The handles are removable and can be attached to the
switch operating shaft through an arc of 360 degrees
in 45 degree increments for maximum mechanical advantage
during operation or may be removed and stored on the
padlockable hanger bracket when not in use. Rotating
the handle toward the desired position causes quick
make/break, spring operated contact movement independent
of the operating handle movement. Latches prevent contact
blow off and provide positive position indication. Additional
features include: padlock provisions in all positions,
bushing oriented line diagram and instructions. Three
position switches are equipped with anti-pass through
provisions to prevent inadvertent operation to the third
position.
Key Interlocks
Are available as required to prevent paralleling feeders
or to limit access to energized equipment or to otherwise
coordinate proper system operation. Keylocks are mounted
on the specified switched ways with locking provided
for the required position.
Automatic Load Transfer Switches
The MiniSub is ideal for maintaining power to critical
loads such as hospitals, airports, shopping centers,
and industrial facilities. Upon loss of preferred primary
feeder voltage, the load is automatically transferred
to an alternate source. Optional automatic retransfer,
overcurrent detection and fault isolation provide additional
system flexibility. Units include fast acting 120 VAC
motor operators attached to the switch operating handles.
Voltage sensing is done through a set of elbow mounted
detectors and relay combination which supply data to
the full function automatic control with self-contained
120 VAC/24VDC control power source. All items are factory
assembled, wired, adjusted, and tested for simplified
installation and operation.
Visible Break, Make and Ground
Each switched way is equipped with a viewing window
for clear, visual confirmation and assurance of contact
position of ALL PHASES. Conforms to local code and operation
practices which require visible break and (where equipped)
visible grounding during system operation, maintenance,
repair, or testing.
Anti-reverse
Operating Handles
Eliminate the possibility of interrupting currents beyond
the capability of the switch by preventing immediate
operation after closing on a fault. A latch on the operating
handle must be reset prior to subsequent operation allowing
upstream circuit protection time to clear the fault.
Primary Cable Terminations
ANSI/IEEE standard 386 defines the specific interfaces
dimensions that 200 and 600 amp, elbows, inserts and
equipment bushings must conform to insure interchangeability.
The 200 amp load break, and 600 amp non load break connectors
provide a convenient and safe way to connect all primary
cables. With the use of a Raychem PILC kit, lead cables
can be connected using the same style. While the cables
and terminations are barriered from access, the elbow
test point offers an additional security and safety,
as well as a voltage reference for automatic or SCADA
type operations This termination provides a deadfront
waterproof connection.
|