What are Transformer Losses?

Transformer losses is the energy efficiency in a transformer. i.e. If the transformer was 100% efficient the losses would be 0 watts.

Oil VS Dry Type Transformer Losses Comparison

MiniSub (Oil Transformer)
Losses
Dry Type Transformer
Losses
KVA Half Load(w) Full Load(w) KVA Half Load(w) Full Load(w)
500
2465
4930
500
5000
10000
750
3950
7900
750
7500
15000
1000
4360
8720
1000
8200
16400
1500
6940
13880
1500
11250
22500
2000
8155
16310
2000
13200
26400
Based
on C802-94

We use the Distributed Power System (DPS)

DPS improves the way of delivering power and reduces the losses in the system and will lower the energy consumption by 10% on average. There is also a reduction in materials used up to 50% and a reduction in installation time by 50%.